For CGC FLORENCE FINCH’s FM200 and Galley Hood Inspections
1. Background and Current Observed Issues
CGC FLORENCE FINCH is requesting inspection and testing for the installed fire suppression
systems in accordance with standard maintenance procedures.
2. REFERENCES
CG MPC R-A-8843, R-102 GALLEY FIRE SUPPRESSION SYSTEM OPERATION TEST/CHECK
CG MPC N30050.D, GALLEY HOOD CONTR FIRE SYS
CG MPC N31015.D FM-200 FIRE PROT SYS (HULLS 33-ON)
3. REQUIREMENTS
Contractor must submit a resume that includes the performance of fire suppression system
maintenance aboard CG assets. Performance of work aboard FLORENCE FINCH must be IAW the
attached MPC’s R-A-8843, N30050.D and N31015.D.
4. PERIOD OF PERFORMANCE
The window of availability for the required services is 22 Jun 2026 to 29 July 2026. All work must be
finalized prior to the end of this window. The Contractor shall contact the Cutter POC upon contract
award and no later than 5 calendar days prior to the start of the availability window to finalize the
exact dates and duration of the service visit. Vendor shall state in their proposal the amount of time
the job is expected to take.
5. PLACE OF PERFORMANCE
CGC FLORENCE FINCH
37573 HIGHWAY 30
ASTORIA OR 97103
USA
Cutter Point of Contact:
MKC Matthew Schmader
PH: (503) 490-8028
Email: Matthew.j.Schmader@uscg.mil
Contracting Officer Technical Representative (COR):
CWO Brandon Triepke
PH: (585) 360-7516
Email: Brandon.m.Triepke2@uscg.mil
-- 1 of 36 --
U.S. COAST GUARD
COMPUTERIZED MAINTENANCE SYSTEM
DAMAGE CONTROL
R-A-8843
REV'D 10/31/19
1 R-102 GALLEY FIRE SUPPRESSION SYSTEM OPERATION TEST/CHECK
SYSTEM:
N3 Firefighting system-General
SUBSYSTEM:
N-300 Firefighting systems-General
COMPONENT:
Extinguishing System, P/N: R-102-1T-02, CAGE: 03670, NIIN: 013699819
PERIODICITY EVENT:
NONE
NUMBER OF COMPONENTS:
1
TASK HOURS:
8.0
PERSONNEL:
1 Contractor
1 DC
1 MK
LOCATION:
Galley
SOURCE DOCUMENTS:
TP 3924-555-A, R-102 Restaurant Fire Suppression System
TP 4563B-555-A, Fire Suppression System-Model R-102
TP 7427-651-A, R-102 Restaurant Fire Suppression System
TP 8057-555-A, Range Hood Fire Fighting System R-102-1T-4N-6F
Distribution Statement D: Distribution authorized to the DHS/CG/DoD and their contractors Administrative/Operational use, 08/08/19. Other requests shall be referred to the
appropriate asset product line.
WARNING: This document contains technical data whose export is restricted by the Arms Export-Control Act (Title 22, U.S.C., Sec 2751, et. seq.) or the Export Administration
Act of 1979, as amended, Title 50, U.S.C. App 2401 et. seq. Violations of these export laws are subject to severe criminal penalties. Disseminate in accordance with
provisions of DoD Directive 5230.25.
DESTRUCTION NOTICE: For classified documents, follow the procedures in DoD 5200.22-M, National Industrial Security Program Operating Manual, Section 5-705 or
DoD 5200.1-R, Information Security Program Regulation, Chapter VI, Section 7. For unclassified, limited documents, destroy by any method that will prevent disclosure of
contents or reconstruction of the document.
Page 1 of 20
-- 2 of 36 --
U.S. COAST GUARD
COMPUTERIZED MAINTENANCE SYSTEM
DAMAGE CONTROL
R-A-8843
REV'D 10/31/19
1 R-102 GALLEY FIRE SUPPRESSION SYSTEM OPERATION TEST/CHECK
REFERENCES:
COMDTINST 9077.1 (series) Equipment Lockout / Tags-Plus Instruction
MPC R-C-8845
MPC R-S-8844
TOOLS/TESTEQUIPMENT:
Cap, Compressed Gas Cylinder, P/N: 77251, CAGE: 03670, NIIN: 014754221
Guard, Mechanical Drive, P/N: 14985, CAGE: 03670, NIIN: 0014408430
Lever, Manual Control, P/N: 14995, CAGE: 03670, NIIN: 014408437
Test Link, Fire, P/N: 15751, CAGE: 03670, NIIN: 012381593
EXPENDABLES:
Cap-Plug, Protective, Dust and Moisture Seal, P/N: 77695, CAGE: 03670, NIIN: 014408427
Link, Fusible, Fire (360 Deg F), P/N: 415745, CAGE: 03670, NIIN: 012422955
CONSUMABLES:
Cover, Pull Station, P/N: 434618, CAGE: 03670, NIIN: 016780181 (If required)
Foam Liquid, Fire Extinguishing (3 Gal), P/N: 79372, CAGE: 03670, NIIN: 014408428 (If required)
Gasket, P/N: 181, CAGE: 03670, NIIN: 004052608 (If required)
Nonmetallic Rod, P/N: 24915, CAGE: 03670, NIIN: 014932964 (If required)
O-Ring, P/N: 56909, CAGE: 03670, NIIN: 012768430 (If required)
Plug, Expansion, P/N: 416974, CAGE: 03670, NIIN: N/A (If required)
Silicone Compound, P/N: AS8660 8OZTU, CAGE: 81343, NIIN: 008807616
Switch, Sensitive, P/N: 423878, CAGE: 03670, NIIN: 014932959 (If required)
Towel, Machinery Wiping, P/N: CJ99300, CAGE: 7J789, NIIN: 006342408
A PRELIMINARY STEPS
WARNING
VARIOUS STEPS IN THIS PROCEDURE EMPLOY ITEMS ON
THE HAZARDOUS MATERIALS LIST. BEFORE EXECUTING
THIS MPC, REFER TO THE APPLICABLE MSDS/SDS FOR
FULL SAFETY AND HANDLING PROCEDURES.
NOTE: This MPC should be completed by Coast guard personnel
who have knowledge of this system or be contracted out. If contrac-
tor performs maintenance on this system, ensure they are an autho-
rized marine fire extinguishing system inspector. If contracted, ship's
force personnel SHALL observe maintenance. Contractor will pro-
vide tools, expendables, and consumables.
1. Notify all cognizant personnel before maintenance is started.
2. Ensure this MPC can be accomplished without disrupting system operations.
3. Obtain permission from Engineering Officer (EO) and Engineering Officer of the Watch (EOW), prior to
conducting maintenance.
DESTRUCTION NOTICE - Destroy by any method that
will prevent disclosure of contents or reconstruction of
the document. Page 2 of 20
-- 3 of 36 --
U.S. COAST GUARD
COMPUTERIZED MAINTENANCE SYSTEM
DAMAGE CONTROL
R-A-8843
REV'D 10/31/19
WARNING
ENSURE EQUIPMENT IS PROPERLY TAGGED OUT. FAILURE
TO COMPLY MAY RESULT IN SERIOUS PERSONAL INJURY
OR DEATH.
4. Complete Red Danger Tag(s) IAW COMDTINST 9077.1 (series).
5. Attach Red Danger Tags to the following:
a. Circuit breaker for galley appliance protected by R-102 system.
b. R-102 system remote pull stations.
c. R-102 system control box.
WARNING
USE APPROPRIATE EYE OR FACE PROTECTION WHEN
EX…