Cold Storage Refrigeration Systems - Small Grains and Potato Germplasm Research Unit

AGRICULTURE, DEPARTMENT OF

Notice type
Combined Synopsis/Solicitation
Solicitation #
1232SA26Q0769
NAICS
238220
PSC
Z1JZ
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Posted
June 10, 2026
Response due
July 6, 2026
Place of performance
Aberdeen, ID

What this opportunity is

The Department of Agriculture is seeking a contractor to replace two cold storage refrigeration systems at the AGL Cold Storage Germplasm Research Unit in Aberdeen, Idaho. This project is set aside for total small business participation under FAR 19.5, making it suitable for small contractors in the HVAC and refrigeration sector. Interested businesses should note that this is a combined synopsis/solicitation, which indicates they will need to track the opportunity closely for bidding details rather than simply responding to a formal solicitation.

Analysis by Mindy, grounded in the SAM.gov notice.

Description

STATEMENT OF WORK 1.0 CONTRACT PROJECT: 1.1 Project Number: 1.2 Project Title: AGL COLD STORAGE FERFRIGERATION SYSTEMS 2.0 PROJECT CONTACT PERSONS: 2.1 Contracting Officer: 2.2 Contracting Officer Representative: Tyler Williams 1691 S. 2700 W. Aberdeen, ID 83210 Phone: (208) 397-8454 Email: Tyler.Williams@usda.gov 2.3 Facility contact Roger Workman 1691 S. 2700 W. Aberdeen, ID 83210 Phone (208) 844-0200 Email: Roger.Workman@usda.gov 3.0 SCOPE OF SERVICES: The Contractor shall furnish all professional services necessary for the accomplishment of the contract project and such required services shall be in accordance with federal, state, and local codes and requirements as described herein and with attached contract documents. At the completion of this project, we expect to have two completely operational refrigeration units and associated systems. 3.1 GENERAL REQUIREMENTS: The Contractor shall be responsible for verifying site conditions, obtaining accurate measurements, and performing any act or operation which may be necessary to properly bid on the work and complete the same as depicted and specified. Failure to verify conditions and obstacles will not relieve the Contractor of the responsibility to complete work as required. 4.0 PROJECT OVERVIEW: The 2025 USDA/ARS Energy Audit and 2020 Facility Condition report has identified the Refrigeration system for the AGL cold storage as needing replaced. This project consists of removal and replacement of two existing cold room refrigeration systems serving the AGL wing cold storage room located within the USDA laboratory building located at 1691 S 2700 W Aberdeen, Idaho 83210. Work includes demolition and removal of existing rooftop condensers, associated refrigerant piping, and interior evaporator units, and the installation of two new refrigeration systems of equivalent capacity utilizing modern low global warming potential (GWP) refrigerants. -- 1 of 4 -- 5.0 SCOPE OF WORK: The Contractor shall provide all labor, materials, equipment, rigging, supervision, transportation, travel and per diem required to complete the work described in this scope. 5.1 EXISTING EQUIPMENT REMOVAL: Disconnect electrical service to two existing refrigeration condensers located on the northeast corner of the laboratory building roof. Recover and evacuate all refrigerant in accordance with EPA regulations. Demolish and remove the existing rooftop condensers, associated refrigerant piping, and two evaporative units located in separate cold storage room inside the USDA laboratory building. All removed equipment shall be transported off-site and disposed of in accordance with applicable regulations. 5.2 NEW REFRIGERATION SYSTEM INSTALLATION: The Contractor shall furnish and install two complete refrigeration systems consisting of rooftop condensing units, interior evaporative units, refrigerant piping, insulation, condensate drainage connections, and electrical disconnects. The systems should provide cooling capacity equivalent to the existing systems and utilize modern refrigerants such as R454 series refrigerant, R32, or approved equivalent. 5.3 CONDENSER INSTALLATION: Two new roof-mounted condensing units shall be installed in the same general location as the existing equipment. Units shall be mounted on appropriately designed strut stands or manufacture-approved roof curbs. The Contractor shall provide crane services necessary for the removal of existing equipment and placement of the new rooftop units. 5.4 ROOF INSPECTION AND MINOR REPAIR: During installation of the new rooftop equipment, the Contractor shall inspect the roof area surrounding the equipment mounting locations. Limited sealing and minor repair shall be performed if roof damage that could lead to leaks is discovered. Major roofing repairs are excluded from this project. 5.5 EVAPORATIVE INSTALLATION: Two new evaporative units shall be installed within separate cold storage room located inside the USDA AGL laboratory wing building. Units shall be mounted in the same location as the existing evaporators and secured to the ceiling structure. The evaporators shall match the load classification of the existing systems and utilize the same refrigerant as the associated condensers. 5.6 REFRIGERANT PIPING: New hard refrigerant piping shall be installed connecting each evaporator to its associated rooftop condenser. Piping shall be routed through the ceiling interstitial space and installed in accordance with applicable mechanical codes and manufacturer requirements. All refrigerant piping shall be insulated in conformance with local mechanical code. -- 2 of 4 -- 5.7 CONDENSATE DRAINAGE: Existing condensate piping shall be reused where serviceable and adequate. If existing piping is found to be insufficient, the Contractor shall install new condensate drain piping. 5.8 ELECTRICAL WORK: The Contractor shall provide and install new electrical disconnects for each new refrigeration unit. This scope does not include installation of new circuit breakers or new branch circuit wiring. Existing wiring shall be reused after verification of appropriate sizing and acceptable condition. 5.9 CONTROLS COORDINATION: The installation shall allow integration of monitoring controls into the refrigeration systems. The building’s current controls provider will perform installation and integration of the monitoring system. The Contractor will coordinate with controls provider and pricing shall be included as part of this contract. Controls shall be utilized for monitoring purposes only and not for system operation. 5.10 SUBMITTALS AND DOCUMENTATION: Prior to equipment procurement, the Contractor shall submit product data and technical documentation for proposed refrigerant equipment for review and approval. Submittals shall include manufacturer data sheets, equipment specifications, refrigerant type, cooling capacity, electrical requirements, equipment dimensions, and installation requirements. 5.11 PROJ

Source: SAM.gov, as posted. Verify the current solicitation before responding.

Pursue this opportunity with Mindy

See who holds it now, who else is bidding, and draft your response — grounded in real government data, not generic AI.

View the original notice on SAM.gov ↗

Similar Active Opportunities (NAICS 238220)