Fire Sprinkler Repairs
GENERAL INFORMATION
CONTRACTING OFFICE’S ZIP CODE*
85723
SOLICITATION NUMBER*
36C26226Q0654
RESPONSE DATE/TIME/ZONE
06-19-2026 1:00 PM MOUNTAIN TIME, DENVER, USA
ARCHIVE
30 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
J012
NAICS CODE*
238220
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs
NCO 22 - Network Contracting
11201 Benton St.
Loma Linda CA 92357
POINT OF CONTACT*
Contract Specialist
Diana McInnis
diana.mcinnis@va.gov
951-601-4352
PLACE OF PERFORMANCE
ADDRESS
Department of Veterans Affairs
NCO 22 - Network Contracting
3601 S. 6th Avenue
Tucson AZ
POSTAL CODE
85723
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
STATEMENT OF WORK
CONTRACT TITLE: Fire Sprinkler repairs
PLACE OF PERFORMANCES:
VA San Diego Healthcare System
3350 La Jolla Village Dr.
San Diego, CA 92161
PERIOD OF PERFORMANCE: 07/01/2026-06/30/2027
CONTRACT TYPE:
Firm Fixed Price
BACKGROUND: Fire sprinkler deficiencies from 2025 annual inspection and testing.
GENERAL REQUIREMENTS:
Per applicable VA San Diego requirements/standards, the contractor will:
BLDG 1 WETPIPE REQUIRED REPAIRS:
**** 6TH FLOOR ****
NORTH: The following areas were found to have 50yr old sprinklers: 6231 (2), 6232 (2), 6233A (2), 6242 (2), 6239 (2), 6240, 6233 (2), 6243 (2), 6254 (6), 6245 (2), 6246 (4), 6246A (2), 6230 (4), 6252B (2), 6252C (1), 6252E (4), 6247 (2), 6249 (2), 6250 (1), 6251 (1), 6254 (6), 6254A (2), 6256 (2), 6257 (2), 6264 (1), 6254B (2), 6263 (2), 6267 (6), 6268 (1), 6269 (2), 6259 (2),6263A (1), 6224 (1), 6225 (1), 6219 (2), 6218 (2), 6217 (4), 6215 (1), 6268 (2). Replace (88) 165° STD ½” Chrome SSP 401chrome trim.
WEST: The following areas were found to have 50yr old sprinklers: 6097 (1), 6024 (1), 6035 (4), 6025 (2), 6032 (2), 6030(4), 6070 (1), 6029 (2), 6083 (2), 6082 (2), 6050 (1), 6045 (2), 6080 (1), 6081 (14), 6062 (3), 6048 (2), 6051 (2), 6049 (2), 6052(5), 6055 (3), 6058 (2), 6061 (2), 6056A (2), 6069 (2), 6074 (2), 6086 (2), 6087 (2), 6088 (4), 6095 (2), 6096 (2), 6091 (1), 6091A(1). Replace (82) 165° STD ½” chrome SSP 401 chrome trim.
SOUTH: The following areas were found to have 50yr old sprinklers: 6105 (3), 6107 (4), 6110 (4) 6118 (2), 6112 (1). Replace(14) 165° STD ½” chrome SSP 401 chrome trim. EAST: The following areas were found to have 50yr old sprinklers: 6149 (1), 6150 (4), 6153 (2), 6160 (1), 6163 (2), 6164 (4),6169 (2), 6170 (2), 6171 (2), 6172 (2), 6176 (2), 6174C (3), 6174G (4), 6174F (4), 6184 (2), 6189A (3), 6189C (2), 6187 (1), 6190(1), 6191 (2), 6192 (2), 6197 (1), 6198 (2) , 6200 (3), 6202 (2), 6203 (2), 6204 (2), 6205 (2), 6207 (2). Replace (66) 165° STD ½”chrome SSP 401 chrome trim.
CORE: Housekeeping closet 6010 replace (1) corroded 155° QR ½” chrome SSP SRC trim.
NORTH: 6254B replace (2) 20yr old 155° QR ½” chrome SSP 399 chrome trim (2001).
NORTH: 6252A next to cage washer door replace (1) corroded 200° QR ½” chrome SSP 401 Chrome trim.
NORTH: 6268 replace (2) 20yr old 155° QR ½” chrome SSP 401 chrome trim (2001).
WEST: refrigerator 6037 replace (2) 20yr old 200° QR 1” x 12” chrome dry pendant w/ chrome trim (2002). NOTE: This will require majority stitch work.
WEST: 6028 replace (2) loaded/corroded 155° QR ½” chrome SSP 401 chrome trim.
WEST: 6044A in 6043 replace (1) corroded 155° QR ½” white SSP SRW.
WEST: 6044 entry replace (1) corroded 155° QR ½” white SSP SRW.
WEST: 6040 women’s bathroom shower replace (1) corroded 155° STD ½” chrome SSP 401 chrome.
WEST: refrigerator 6081E replace (1) 10yr old 200° STD 1” x 12” chrome dry pendant w/ chrome trim (2013). NOTE: this will require majority stitch work.
WEST: 6070 refrigerator replace (1) 10yr old 200° STD 1” x 12” chrome dry pendant w/ chrome trim (2013). NOTE: this will require majority stitch work.
WEST: 6056A & 6057 replace (2) 20yr old 155° QR ½” chrome SSP SRC trim (2001).
WEST: 6062 replace (3) 20yr old 155° QR ½” chrome SSP 401 chrome trim (2002).
WEST: 6070 replace (1) 20yr old 155° QR ½” white SSP SRW trim (2004).
WEST: 6091 & 6091A replace (2) 20yr old 155° QR ½” chrome SSP 401 chrome trim (2002).
SOUTH: 6104 refrigerator replace (1) 10yr old 200° STD 1” x 12” chrome dry pendant w/ chrome trim (2013). NOTE: this will require majority stitch work.
SOUTH: 6108A replace (4) corroded 165° STD ½” chrome SSP 401 chrome trim.
SOUTH: 6112 replace (1) 20yr old 155° QR ½” chrome SSP 401 chrome trim (2005).
SOUTH: 6112 refrigerator replace (1) 10yr old 200° STD 1” x 12” chrome dry pendant w/ chrome trim (2013) this will require majority stitch work. NOTE: Inside refrigerator is very warm!
EAST: hallway leading to stair 12 replace (9) corroded 155° STD ½” white SSP 401 white trim.
EAST: 6155 replace (2) corroded 165° STD ½” chrome SSP 401 chrome trim.
EAST: refrigerator 6166 replace (2) 10yr old 200° QR 1” x 12” chrome dry pendant w/ chrome trim (2013). NOTE: this will require majority stitch work.
EAST: 6179 replace (2) corroded 165° STD ½” chrome SSP 401 chrome trim
EAST: 6197A in 6198 replace (3) corroded 165° STD ½” chrome SSP 401 chrome trim
**** 5TH FLOOR ****
SOUTH: exterior core hallway from stair 11 to dead end into east wing replace (7) corroded 155° QR ½” White SSP 401 white trim.
NORTH: exterior core hallway to stair 9 replace (5) corroded 155° QR ½” white SSP 401 white. These Sprinklers are also near 20yrs old (2008).
NORTH: hallway outside 5315 replace (1) corroded 155° QR ½” chrome SSP SRC trim.
WEST: 5004 next to 5003 men’s bathroom replace (2) corroded 155° QR ½” chrome SSP 401 chrome Trim.
CORE: hallway to south wing door replace (4) 20yr old 155° QR ½” chrome SSP SRC trim.
CORE: 5019 replace (1) 20yr old 155° QR ½” chrome SSP SRC trim.
CORE: 5020 repl…