Description
Three-Year Electrical System Preventive Maintenance Survey
Performance Work Statement (PWS)
PART 1
General Information
1.0 General
This is a non-personnel service contract to provide all labor, material, tools, equipment, and
personal protective equipment (PPE) to perform required testing on the electrical distribution
system according to National Fire Protection Association (NFPA) 70B, the Joint Commission and
the ANSI/NETA MTS-2019 at the Chalmers P. Wylie VA Ambulatory Care Center (VAACC) which
includes Main Building, Energy Center, Engineering Building, and Parking Garage. Work shall
be performed by journeyman electricians qualified for the voltage level of the various
equipment. Due to the nature of the work, all work will be performed during non-business
hours. All work shall be coordinated with Engineering Service. Contractor shall schedule work
at least 8 weeks in advance to assure proper coordination with facility staff. The Government
shall not exercise any supervision or control over the contract service providers performing the
services herein. Such contract service providers shall be accountable solely to the Contractor
who, in turn is responsible to the Government.
http://www.netaworld.org/standards/ansi-neta-mts
1.1 Contracting Officer’s representative (COR)
The Contracting Officer’s Representative (COR) will be the principal liaison for the Contractor
during the duration of the contract and must be contacted prior any performance on
equipment.
1.2 Specific Tasks
The contractor shall perform maintenance according to NFPA 70B, Attachment 2 ANSI/NETA
MTS-2019 7.0 to 8.0 including primary injection testing according to the Electrical Equipment
Listing.
At a minimum, the work shall include the following:
-- 1 of 6 --
- Transformers of 500KVA or larger shall be cleaned interiorly, inspected for signs of
overheating and inspected for any damages to the housing, connection points, or
insulation.
- Dry type transformers must be thoroughly cleaned, both interior and exterior, and
inspected for overheating.
- Electrical equipment (including, but not limited to Automatic Transfer Switches (ATS)
switchgears, switchboards, distribution panels, motor control centers, and all related
components) are required to be inspected, tested, maintained, and/or calibrated as
follows:
• Use lint-free rags to clean conductors, contact points between the circuit
breakers and main buss bars, buss bars and interior of the electrical
equipment. Use a vacuum cleaner to remove large debris; COMPRESSOR AIR
IS NOT TO BE USED FOR THIS PURPOSE. Visually inspect for signs of
overheating, misaligned contacts, damage insulation, or lose lugs.
• Lubricate all moving parts with manufacturer’s approved lubricants
• Test and exercise circuit breakers located in switchgears, switchboards,
distribution panels to ensure operation under overload and short circuit
conditions. The VA will provide updated short circuit study for all circuit
breaker adjustments according to the recommended setting by the study.
• Test ground fault protection devices for proper function if they are installed
in the Electrical Power Distribution System.
• Inspect and tighten ground connections. Test ground resistance for the
entire facility grounding system.
• Identify hot spots in the electrical equipment. This work must be done while
the Electrical Power Distribution System is energized. Appropriate safety
precautions must be taken before, during and after scanning the system.
Objective of this work is to detect any loose, broken, or corroded
connections in the system. Problem connections shall be replaced with new
connectors, and/or tightened with torque wrench to meet the equipment
manufacturers’ specifications. No longer a contractor requirement
• Calibrate and maintain adjustable protective relays.
• Test all control systems equipment for proper operation after maintenance is
performed and before placing them back in operation.
• Full testing shall be performed for all breakers rated above 200 Amps
throughout the facility.
- Provide complete written report of the work performed to the VAACC within fourteen
(14) days of completion. Information shown in the report shall be as follow:
• Company’s name, address, telephone and fax numbers.
-- 2 of 6 --
• Name and signature of contractors who perform the maintenance and
testing.
• VA Work Contract Number, name and number of VA Contracting Officer.
• Date and Time of Work.
• Copies of contractors’ valid license, professional and training certificates.
• Descriptions and model number of specialized tools and equipment used,
such as torque wrench, infrared scanning camera, etc.
• Location, type, name, and nameplate information of electrical equipment to
be maintained and tested.
• Description of work items.
• Test data.
• Submit three (3) hard copies of the complete written report, and one (1) CD-
Rom of the electronic version of the report in Microsoft Word format to the
COR within fourteen (14) calendar days of work.
• Provide recommendations for any repair, replacement, or other potential
corrective action that should be taken as a result of the test. For any devices
tested which do not pass testing or inspection, the COR must be notified
immediately, as well as documenting the information in the report.
- Columbus VA ACC will be responsible for contacting American Electric Power (AEP) to
disconnect and reconnect main feed to the Facility.
- Contractor has no more than 30 days after award to commence work and 180 days for
all work to be complete, unless prior coordination has been made and approved by the
Government
- Site visit is strongly recommended.
1.3 Contractor Qualifications
Contractor shall be certified by the InterNational Electrical Testing Association (NETA) as NETA
Certified Technician, and completed the Occupational Safety & Health Administration (OSHA)
approved 10-hour construction safety training. Contractors shall have technical trainings, and
track records of working exp…
Source: SAM.gov, as posted. Verify the current solicitation before responding.