Replace Fuel Tanks and Associated Lines - Rec Camp
DEPT OF DEFENSE
Notice type
Solicitation
Solicitation #
FA303026Q0012
NAICS
237120
PSC
Z2NA
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Posted
June 11, 2026
Response due
June 17, 2026
Place of performance
San Angelo, TX
What this opportunity is
The Department of Defense is seeking a contractor to replace two above-ground fuel tanks and associated lines at Goodfellow Air Force Base Recreation Camp in Texas. This project is set aside for total small businesses under NAICS 237120, which suits contractors specializing in construction and facility maintenance. Interested businesses should note that this is a solicitation notice, indicating they should prepare to submit bids rather than simply track the opportunity.
Analysis by Mindy, grounded in the SAM.gov notice.
Description
1
STATEMENT OF WORK
FOR
REPLACE FUEL TANKS AND ASSOCIATED LINES
FAC #57140
OP #1148702
January 2026
PREPARED BY:
17TH CIVIL ENGINEER SQUADRON (AETC)
460 E. KEARNEY BOULEVARD
GOODFELLOW AFB, TX 76908-4104
-- 1 of 14 --
2
Table of Contents
PART 1.0 - SUMMARY ............................................................................................................. 3
PART 2.0 - PARTS ..................................................................................................................... 6
PART 3.0 - EXECUTION ........................................................................................................... 6
PART 4.0 - SPECIAL CONDITIONS & PERMITS ................................................................ 8
PART 5.0 - ENVIRONMENTAL REQUIREMENTS............................................................ 11
PART 6.0 - COMPLETION OF WORK .................................................................................15
-- 2 of 14 --
3
PART 1.0 - SUMMARY:
1.1 GENERAL: The work to be performed under this contract and in accordance with this
Statement of Work shall consist of furnishing all necessary parts, labor, tools, transportation,
supplies, supervision, equipment, materials, and incidentals necessary for providing all work
shown in the project documents, and all applicable codes, regulations, standards, and criteria in
effect at the date of solicitation.
1.2 PROJECT DESCRIPTION: The two (2) above ground fuel storage tanks were installed in
1993 are experiencing corrosion with one being in operable condition with potential to fail and
leak to become hazardous to the nearby lake area. The tanks service two fuel dispense pumps for
watercraft.
The Contractor shall remove existing two (2) 500-gallon above ground steel industrial fuel tanks
and all piping and parts associated with existing fuel tanks at Goodfellow AFB Recreation Camp.
The Contractor shall install one (1) new Double – Walled 500-gallon Fuel Storage Tank –
UL2085 – Fireguard – Above-Ground Fuel Storage Tank or approved equal and all associated
parts.
1.3 LOCATION: Goodfellow AFB Recreation Camp is located near Lake Nasworthy at 1950 E
Concho Dr. Tom Green County, San Angelo, TX. The work on the Recreation Camp is for
Facility #57140. See attached Technical Exhibits for location of fuel tanks. (TE-1).
1.4 REFERENCES: The Contractor shall identify and comply with all applicable federal, state,
and local laws; statutes; Executive Orders; Department of Defense/Air Force manuals,
handbooks, regulations, guidance, and policies. The Contractor shall comply with the National
Institute of Building Sciences’ Whole Building Design Guide Construction Criteria Base Unified
Facility Criteria (UFC) and all related libraries. It is the Contractor’s responsibility to identify
and comply with all applicable requirements. In addition to the documents referenced above, all
publications listed herein shall be the most current editions in effect at the time of solicitation
and form a part of this SOW:
UNIFIED FACILITIES CRITERIA (UFC) 3-460-01 DESIGN: PETROLEUM FUEL
FACILITIES
2024 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 31- STANDARD FOR THE
INSTALLATION OF OIL-BURNING EQUIPMENT
2024 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 30 – FLAMMABLE AND
COMBUSTIBLE LIQUIDS CODE
2024 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 30A – CODE FOR MOTOR
FUEL DISPENSING FACITLITIES AND REPAIR GARAGES
-- 3 of 14 --
4
CODE OF FEDERAL REGULATIONS (CFR) TITLE 40
WHOLE BUILDING DESIGN GUIDE (WBDG)
AIR FORCE MANUAL (AFMAN) 32-1065 GROUNDING AND ELECTRICAL SYSTEMS
1.5 SITE VISITS: The Contractor may visit the premises to become thoroughly familiar with
details of the work and working conditions, verify dimensions in the field, and shall advise the
Contracting Officer of any discrepancies before starting work.
1.6 WORK AND MECHANICS: The work for this project shall be executed in the best and most
workmanlike manner. Individual trade work for this project shall be performed and quality
maintained by the applicable trade, only. All trades shall coordinate their work with that of other
trades. The Contractor shall coordinate and perform all operations in a manner that will result in
a professional and expeditiously completed project. The work shall be in strict accordance with
prevailing industry standards and manufacturer’s instructions.
1.6.1 PERFORMANCE PERIOD: The period of performance for all work shall be one hundred
and twenty (120) calendar days.
1.6.2 WORKING CONDITIONS: Working hours for the contractor will normally be between the
hours of 7:30 A.M. and 4:30 P.M. excluding Saturdays, Sundays, Federal holidays, and days
designated as “Family Days” by Air Education and Training Command (AETC). See the table
below for reference for the 2025-2026 dates and refer to Section H of the solicitation /contract
document for further information on working days. Any holiday falling on a Saturday will be
observed the preceding Friday. Any Holiday falling on a Sunday will be observed the following
Monday.
If the Contractor desires to work during periods other than above, a request must be made to the
Contracting Officer in writing three (3) calendar days in advance of his/her intention. If the
required base personnel are reasonably available, the Contracting Officer may authorize the
Contractor to perform work during periods other than normal duty hours/days.
-- 4 of 14 --
5
2026
Federal Holiday Holiday Family
New Year’s Day 01 Jan 02 Jan
Martin Luther King’s B-day 19 Jan
Washington’s Birthday 16 Feb
Memorial Day 25 May 22 May
Juneteenth 19 Jun 22 Jun
Independence Day 03 Jun 06 Jul
Labor Day 07 Sep 04 Sep
Columbus Day 12 Oct
Veterans Day 11 Nov
Thanksgiving Day 26 Nov 27 Nov
Christmas Day 25 Dec 24 & 31 Dec
The base could be closed because of security problems, adverse weather, or other events. Unless
otherwise notified by the Government, the Contractor should monitor local television stations,
radio stations, or Goodfel…
Source: SAM.gov, as posted. Verify the current solicitation before responding.
Pursue this opportunity with Mindy
See who holds it now, who else is bidding, and draft your response — grounded in real government data, not generic AI.
View the original notice on SAM.gov ↗Similar Active Opportunities (NAICS 237120)
Jet A Fuel Storage Tank Systems
AGRICULTURE, DEPARTMENT OF · Combined Synopsis/Solicitation · due June 23, 2026
Jet A Fuel Storage Tank Systems
AGRICULTURE, DEPARTMENT OF · Combined Synopsis/Solicitation · due June 18, 2026
Z--Remove and Replace Above Ground Fuel Storage Fuel
INTERIOR, DEPARTMENT OF THE · Combined Synopsis/Solicitation · due July 18, 2026
Y1NA--CON | NRM 653-23-100 | Remove Replace Underground Fuel Tanks
VETERANS AFFAIRS, DEPARTMENT OF · Solicitation · due June 17, 2026
Solicitation for Grand Forks Fueling System Repairs
DEPT OF DEFENSE · Solicitation · due July 10, 2026
Y1NA--CON | NRM 653-23-100 | Remove Replace Underground Fuel Tanks
VETERANS AFFAIRS, DEPARTMENT OF · Solicitation · due June 17, 2026