Y1DA--Project # 596A4-24-101 - Construction to Replace Main Electrical Distribution Equipment
VETERANS AFFAIRS, DEPARTMENT OF
Notice type
Solicitation
Solicitation #
36C24926R0073
NAICS
236220
PSC
Y1DA
Posted
July 1, 2026
Response due
July 31, 2026
Description
Replace Main Electrical
Distribution Equipment
Project Number: 596A4-24-101
Bid Documents
Coordination Study
Northeast Infrastructure, LLC
34 Brown Street
Honesdale, PA 18431
October 29, 2025
Lexington VAHCS
Troy Bowling Campus
1101 Veterans Dr.
Lexington, KY 40502
-- 1 of 31 --
LEXINGTON KY, VA MEDICAL CENTER
MEDIUM VOLTAGE
FAULT CURRENT AND
COORDINATION STUDY
NEW SWITCHGEAR
100% SUBMITTAL
PROJECT NUMBER: 240121
31 OCTOBER 2025
Prepared By:
Elizabeth Tuomey, PE
Checked By:
Daniel Morton, PE
-- 2 of 31 --
Medium Voltage Fault Current and Coordination Study 31 October 2025
Lexington VAMC New Switchgear TOC-1
TABLE OF CONTENTS
1 EXECUTIVE SUMMARY ....................................................................................................1-1
1.1 Introduction ...................................................................................................................................................... 1-1
1.2 Calculations ....................................................................................................................................................... 1-1
2 SHORT CIRCUIT ANALYSIS .............................................................................................2-1
2.1 Introduction ...................................................................................................................................................... 2-1
2.2 Short Circuit Calculation Results............................................................................................................ 2-1
2.3 Equipment Evaluation Results ................................................................................................................ 2-1
3 PROTECTIVE DEVICE COORDINATION .......................................................................3-1
3.1 Introduction ...................................................................................................................................................... 3-1
3.2 Time-Current Characteristic Coordination Sheets ....................................................................... 3-1
APPENDIX
A Short Circuit Current Calculation – Worst Case Single Source Scenario
B One-line Diagram Scope of Coordination
C Time Current Coordination Curves
D Protective Device Settings
E KU Short Circuit and Protective Device Data
-- 3 of 31 --
Medium Voltage Fault Current and Coordination Study 31 October 2025
Lexington VAMC New Switchgear 1-1
1 EXECUTIVE SUMMARY
1.1 INTRODUCTION
Wiley|Wilson is providing the medium voltage design for the Lexington VA Medical Center
to replace the Tower Building Switchgear, Chiller Switchgear 1, and associated distribution
equipment. The purpose of this calculation package is to present the Short Circuit and
Coordination Studies included with the design.
The new Tower switchgear consists of a 1200A 12.47kV double-ended four-section metal-
clad switchgear, in a main-tie-main configuration. Each half of this switchgear consists of
one main and two feeder breakers, with a tie breaker between them. The switchgear mains
are fed from two separate feeder breakers in the VA-owned Main Building Switchgear that
is immediately upstream. Also included in this design is the replacement of the 480V
network protectors with high pressure safety switches on the secondary side of each of four
Tower Building service transformers.
The Chiller Switchgear consists of a unit-substation-like lineup, with a 480V double-ended
switchgear in a main-tie-main configuration, each side fed by a 2500kVA dry-type 12470-
480V transformer and its associated 600A freestanding metal-clad circuit breaker.
The short circuit study is intended to show minimum required equipment ratings with the
designed feeder lengths. Another analysis will be required during construction to reflect
actual conditions based on purchased equipment and installed feeder types and lengths.
A coordination study has been performed for the medium voltage system using basis of
design equipment to prove that proper coordination can be achieved. The Contractor will
be required to provide their own coordination study based on actual equipment purchased
to ensure that the equipment can meet code and project requirements.
1.2 CALCULATIONS
This study includes short circuit calculations and overcurrent protective device
coordination.
All calculations have been performed using Power*Tools for Windows, a modular assembly
of software developed by SKM Systems Analysis, Inc. The following modules have been used
for this study:
• System Model Development DAPPER
• Short Circuit Calculations A_Fault
• Protective Device Coordination CAPTOR
-- 4 of 31 --
Medium Voltage Fault Current and Coordination Study 31 October 2025
Lexington VAMC New Switchgear 1-2
Version 10.0.0.1 of the Power*Tools software has been used for all of the calculations
presented throughout this report. Additional information related to this software package
can be found at www.skm.com.
For this study, the purpose of the short circuit calculations is to determine available short
circuit current levels throughout the electrical distribution system. The results of these
calculations are used to confirm the short circuit interrupting and withstand ratings of
designed equipment. These results can be found in Section 2 – “Short Circuit Analysis.”
During the protective device coordination study, the ratings and settings of the proposed
overcurrent protective devices are examined. In a selectively coordinated system, the
protective device closest to the fault will interrupt the circuit thereby minimizing the
disruption of electrical service. We have developed and plotted time current characteristic
(TCC) coordination sheets showing the relationships between the relays in the Tower
switchgear and the relays in the chiller switchgear transformer primary disconnects, the
relays for the Main Switchgear breakers that feed them, the trip units in the contact switches
and chiller switchgear main breakers, and…
Source: SAM.gov, as posted. Verify the current solicitation before responding.
Pursue this opportunity with Mindy
See who holds it now, who else is bidding, and draft your response — grounded in real government data, not generic AI.
View the original notice on SAM.gov ↗Similar Active Opportunities (NAICS 236220)
Matsushima JASDF Base Storage Shelter
DEPT OF DEFENSE · Sources Sought · due August 7, 2026
NAF Outdoor Recreation/Equipment Rental Center, Kadena Air Base, Okinawa, Japan
DEPT OF DEFENSE · Solicitation · due July 24, 2026
Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler
VETERANS AFFAIRS, DEPARTMENT OF · Presolicitation · due September 8, 2026
Repair Windows Basewide, 126 ARW, Scott AFB
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due August 14, 2026
Z1DA--| SOL| NRM| 646-21-101 UD SPS AHU & RO Upgrade Construction (VA-26-00036217)
VETERANS AFFAIRS, DEPARTMENT OF · Solicitation · due August 27, 2026
UNICOR Elevator Modernization Project
JUSTICE, DEPARTMENT OF · Combined Synopsis/Solicitation · due August 28, 2026