Description
PR #: 31040PR270000084
STATEMENT OF WORK
LAST UPDATED: 11/12/2026 PAGE 1/6
STATEMENT OF WORK (SOW)
FOR
USCG Base Portsmouth Main Switchgear Cleaning, Visual Inspection, Breaker
Servicing, Battery Replacement and DC Control Power Maintenance
1.0 GENERAL
1.1 SCOPE
The Contractor shall furnish new batteries and all necessary labor, tools, specialized equipment,
personal protective equipment (PPE), materials, and certified technicians to inspect and clean
the switchgear vertical sections. Switchgear DC Control Battery Replacement & Charger
Operational Check. Verify de-energization, zero energy verification, and apply facility-approved
LOTO protocols. If work on the control battery system must occur while switchgear is online,
strict DC arc/shock protective boundaries must be enforced.
2.1 TASK ONE. Switchgear Vertical Sections: Inspection and Cleaning
2.1.1 Vacuum and clean exterior panels, louvers, filters, and access doors.
2.2.2 Clean switchgear interior compartments. Wipe down insulators, busbar supports, and
barriers. Ensure louver screens and ventilation pathways are clear of dust and debris. Clean
breaker frames, operating linkages, and arc chutes.
2.2.3 Inspect hinges, latches, interlocks, and door gaskets for physical damage, binding,
or deterioration. Inspect internal vertical sections, busbars, supports, and insulators.
2.2.3 Rack out/draw out the One (1) 1200A Main Breaker , Three (3) 1200A Feeder/Breakers
One (1) Generator Breaker 1200 A into the disconnected/test position (or remove to breaker
maintenance cart).
2.2.4 Inspect primary stabs, finger clusters, ground shoes, and secondary disconnect contacts for
signs of wear, burning, galling, or misalignment. Inspect arc chutes, inter-phase barriers,
and charging mechanism assemblies.
2.2.5 Provide a inspection report to the USCG
2.2 TASK TWO. Switchgear DC Control Battery Replacement & Charger Operational
Check
2.2.1 Safely isolate and disconnect the existing four (4) 12V 32A control power batteries.
Remove old batteries and dispose of/recycle them in strict accordance with EPA
and local environmental regulations (provide recycling manifests).
-- 1 of 6 --
PR #: 31040PR270000084
STATEMENT OF WORK
LAST UPDATED: 11/12/2026 PAGE 2/6
2.2.2 Clean battery rack/tray, inspecting for acid damage, rust, or structural integrity
issues. Apply neutralizing wash if necessary.
2.2.3 Supply and install four (4) new OEM-equivalent 12-volt, 32-amp batteries. Clean,
treat, and torque all inter-cell connectors, terminals, and cable using anti-
corrosion grease and calibrated torque tools
2.2.2 Energize the installed battery charger and verify proper DC output polarity and system
connection. Measure and document open-circuit and loaded output voltage.Verify charger
operating modes.
2.2.3 Test functional charger alarms and indicators (e.g., AC Failure, Low DC Voltage, High DC
Voltage, Ground Fault detection). Verify that the switchgear trip and close control circuits
receive steady, uninterrupted DC control voltage.
3.0KEY PERSONNE
Project Manager
3.1 PROJECT MANAGER
3.1.1 The Project Manager must be available to the QAE via telephone between the hours of
0700 and 1530 EST, Monday through Friday, and must respond to a request for discussion or
resolution of technical problems within 24 hours of notification.
3.2 EMPLOYEE IDENTIFICATION
3.2.1 The QAE will provide a Base Access request form. The Contractor will need to return the
Base Access form with list of all employees to the QAE Representative five (5) days prior to
commencing work. The USCG Base Portsmouth Security Office will be given a copy of the
employee list, and a pass will be issued for entry. A valid state license plate and safety
inspection sticker is required. All vehicles operated on government property shall be maintained
in a good state of repair.
3.3 EMPLOYEE CONDUCT
Contractor’s employees must comply with all applicable Government regulations, policies and
procedures (e.g., fire, safety, sanitation, environmental protection, security, and possession of
weapons) when visiting or working at Government facilities. The Contractor must ensure
Contractor employees present a professional appearance at all times and that their conduct
must not reflect discredit on the United States or the Department of Homeland Security. The
Project Manager must ensure Contractor employees understand and abide by Department of
Homeland Security established rules, regulations and policies concerning safety and security.
3.4 REMOVING EMPLOYEES FOR MISCONDUCT OR SECURITY REASONS
The Government may, at its sole discretion (via the Contracting Officer), direct the Contractor to
remove any Contractor employee from DHS facilities for misconduct or security reasons.
Removal does not relieve the Contractor of the responsibility to continue providing the services
-- 2 of 6 --
PR #: 31040PR270000084
STATEMENT OF WORK
LAST UPDATED: 11/12/2026 PAGE 3/6
required under the contract. The Contracting Officer will provide the Contractor with a written
explanation to support any request to remove an employee.
3.5 SITE VISIT
A site visit is recommended to conduct field verification of any/all quantities and measurements
before submitting bids. Interested parties shall make arrangements for a site visit with the QAE.
3.5.1 DESIGNATED CONTRACTING OFFICER’S QA EVALUATOR (QAE)
REPRESENTATIVE
Nathan Chappell. (206)815-2176 Nathan.C.Chappell@uscg.mil.
3.5.2 All site visits are to be pre-arranged a minimum of three (03) days in advance. To arrange
a site visit, the QAE will email a base access form to be filled out.
3.5.3 CONDITIONS AFFECTING THE WORK
The Offeror should visit the site and take such other steps as may be reasonably necessary to
ascertain the nature and location of the work, the general and local conditions which can affect
the cost of the work thereof. Failure to do so will not relieve bidders from responsibility for
estimating properly the difficulty or cost of successfully performing the work. The government…
Source: SAM.gov, as posted. Verify the current solicitation before responding.
Pursue this opportunity with Mindy
See who holds it now, who else is bidding, and draft your response — grounded in real government data, not generic AI.
View the original notice on SAM.gov ↗Open opportunities in NAICS 811310
Equipment Operations, Maintenance, and Repair Services at Joint Base Pearl harbor Hickam, Hawaii (JBPHH).
DEPT OF DEFENSE · Solicitation · due December 8, 2026
J061--Emergency Switchgear Repairs PWS 539
VETERANS AFFAIRS, DEPARTMENT OF · Sources Sought · due December 7, 2026
US Army Hawaii Dining Facilities’ Large Equipment Preventative Maintenance & Repair Services
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due November 30, 2026
USCG Station Fire Island Attic Vents
HOMELAND SECURITY, DEPARTMENT OF · Solicitation · due November 30, 2026
FIRE EXTINGUISHER INSPECTION, MAINTENANCE, RECHARGE, REPAIR, HYDROSTATIC TESTING
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due December 2, 2026
Crane Hoist and Conductor Bar Upgrade
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due December 9, 2026