HVAC Preventative Maintenance for Fort Hall Service Unit, Fort Hall, ID
HEALTH AND HUMAN SERVICES, DEPARTMENT OF
Notice type
Sources Sought
Solicitation #
REQT-IHS-2026-00357
NAICS
238220
PSC
J041
Set-aside
No Set aside used
Posted
November 19, 2026
Response due
December 4, 2026
Place of performance
Fort Hall, ID
What this opportunity is
The Department of Health and Human Services is seeking vendors for preventative maintenance services on the HVAC system, chiller, and controls at the Fort Hall Service Unit in Fort Hall, ID. This opportunity is open to all business types, including native small businesses, with a focus on compliance with ASHRAE standards for healthcare ventilation. As a Sources Sought Notice, this is not a solicitation for bids but rather a request for information to gauge vendor capabilities, so interested parties should track this opportunity for future solicitation announcements.
Analysis by Mindy, grounded in the SAM.gov notice.
Description
1. Title
Preventative maintenance service agreement for the HVAC system, Chiller and Controls at the Fort Hall Service Unit (FHSU), Fort Hall, ID.
2. Background
The Fort Hall Service Unit is accredited by the Accreditation Association for Ambulatory Health Care (AAAHC). The FHSU continually demonstrates a clinic-wide effort to maintain the highest standards of care and to improve the health status of their patients. FHSU specializes in the promotion of comprehensive family healthy for federally recognized American Indian and Alaska Native people and their descendants. The clinic requires preventative maintenance of the HVAC system to optimize facility operations and energy efficiency without interruptions to patient care.
3. Scope
Perform preventative maintenance services on the HVAC system, Chiller and Controls to ensure the facility is ventilated in accordance with the most current version of ASHRAE 170 – Ventilation of Health Care Facilities, and ASHRAE 62.1 – Ventilation for Acceptable Indoor Air Quality.
4. Specific Tasks or Specifications
Preventative Maintenance Tasks: At a minimum, the following task shall be completed unless the manufacture’s recommendations require additional task or intervals.
Air Handlers Units, Mixed Air, 25 HP (QTY=1), 3/4 HP (QTY=3). Return Air Fan, 10 HP (QTY=1).
Comprehensive – Minimum 1 per yearCheck with appropriate customer representative for operational deficiencies
Visually inspect damper(s)
Check condition of pulleys and belts
Check for proper fan operation
Check condition of coils
Check condition of filters
Record temperatures and pressures (if applicable)
Check for unusual noise and vibration
Check for deterioration of gaskets and seals
Check overall condition of unit
Visually inspect for fluid leaks of coils and connecting piping
Check starter/contactor
Check and tighten electrical connections
Check damper operation and lubricate as required
Visually check control valve(s)
Lubricate blower and motor bearings
Clean condensate pan and clear drain line
Check condition of blower assembly
Remove and dispose of any debris from any maintenance activity
Document tasks performed during visit and report any observations to appropriate customer representative
Operational – Minimum 1 per year Check with appropriate customer representative for operational deficiencies
Inspect motor mounting isolators
Check for integrity of cabinet hardware
Visually inspect damper(s)
Verify damper operation
Check condition of pulleys and belts
Check for proper fan operation
Check condition of coils
Check condition of filters
Record temperatures and pressures (if applicable)
Check condensate drain
Visually inspect electrical connections
Check for unusual noise and vibration
Check overall condition of unit
Visually inspect for fluid leaks of coils and connecting piping
Document tasks performed during visit and report any observations to appropriate customer representative
Belt Change – As needed
Check with appropriate customer representative for operational deficiencies
Perform belt change procedures
Remove and dispose of any debris from any maintenance activity
Document tasks performed during visit and report any observations to appropriate customer representative.
Coil Cleaning – Minimum 1 per year
Check with appropriate customer representative for operational deficiencies
Clean condensate drain (if necessary)
Spray coil(s) with chemical solution
Rinse coil(s) thoroughly with water
Remove and dispose of any debris from any maintenance activity
Document tasks performed during visit and report any observations to appropriate customer representative
Exhaust Fans, EF ½ HP (QTY=1), EF ¼ HP (QTY=3), IEF ¼ HP (QTY=1), BEF ¼ HP (QTY=1)
Comprehensive – Minimum 1 per yearCheck with appropriate customer representative for operational deficiencies
Check condition of pulleys and belts
Check for proper fan operation
Record temperatures and pressures (if applicable)
Check for unusual noise and vibration
Check overall condition of unit
Check and tighten electrical connections
Check condition of blower assembly
Remove and dispose of any debris from any maintenance activity
Document tasks performed during visit and report any observations to appropriate customer representative
Operational – Minimum 1 per year Check with appropriate customer representative for operational deficiencies
Check condition of pulleys and belts
Record temperatures and pressures (if applicable)
Visually inspect electrical connections
Check for unusual noise and vibration
Check overall condition of unit
Document tasks performed during visit and report any observations to appropriate customer representative
Belt Change – As needed
Check with appropriate customer representative for operational deficiencies
Perform belt change procedures
Remove and dispose of any debris from any maintenance activity
Document tasks performed during visit and report any observations to appropriate customer representative.
Boilers, Gas-Fired, 850 Sonic Condensing (QTY=2)
Comprehensive – Minimum 1 per yearCheck with appropriate customer representative for operational deficiencies
Inspect burner/oil pump contactors for wear
Check and tighten electrical connections
Check for proper gas supply pressure
Check oil pump for proper operation
Check and clean pilot assembly
Clean combustion fan wheel
Visually inspect combustion chamber, draft diverter and flue for accumulation of soot - clean as needed
Check burner for proper sequence of operation
Check operating controls
Check all safety controls
Lift relief valve to ensure proper operation
Check boiler relief valves for leakage
Check combustion blower motor operation and lubricate as needed
Check for proper operation of oil preheaters (if applicable)
Check factory supplied oil and gas piping and components for leakage
Drain boiler, open hand hole covers and clean as needed (if …
Source: SAM.gov, as posted. Verify the current solicitation before responding.