Open for responses
J061--Emergency Switchgear Repairs PWS 539
VETERANS AFFAIRS, DEPARTMENT OF
Notice type
Sources Sought
Solicitation #
36C25027Q0125
NAICS
811310
PSC
J061
Posted
November 24, 2026
Response due
December 7, 2026
Description
Page 1 of 17
Performance Work Statement Repair Emergency Power Phase 2
Cincinnati VA Medical Center
1. GENERAL
1.1. Purpose
The Department of Veterans Affairs requires the services of a qualified contractor to repair,
program, modify, and test the emergency power generation and paralleling switchgear system
serving at Building 1 at the Cincinnati VA Medical Center.
Last year, the lack of backup generators and emergency power led to operating room closures at
Cincinnati VA Medical Center. If the sole generator fails, critical care cannot be maintained
onsite. As a result, all critical care would need to be diverted to other VA facilities or community
care providers.
The system is currently operating with only one functional generator. This condition leaves the
facility without the required redundancy in the event of a utility outage or failure of the
remaining operational generator. The purpose of this requirement is to restore both generators
to operational status, repair the associated paralleling switchgear, and verify that the
emergency power system operates as designed.
1.2. Scope
The Contractor shall provide all labor, supervision, materials, parts, equipment, tools,
programming, testing equipment, transportation, and incidental services necessary to:
1. Repair both emergency generators.
2. Replace damaged MFR13 and reverse power protective relays associated with the
paralleling switchgear.
3. Modify the switchgear door and wiring as required to support the replacement relays.
4. Update applicable ABB system drawings.
5. Program and test the replacement relays.
6. Provide load-bank testing for both generators.
7. Test the paralleling operation of Generators 1 and 2.
8. Verify generator priority changes, automatic return to service, and load shedding.
9. Test the generator control panels.
10. Complete an operational test of the entire emergency power system following all repairs.
1.3. Period of Performance
The period of performance shall be 120 days.
-- 1 of 17 --
Page 2 of 17
Generator work shall be performed on two separate weekends, with one generator serviced
during each weekend. Specific dates shall be coordinated with and approved by the
Government before work begins.
The Contractor shall perform work on Saturdays and Sundays unless otherwise approved in
writing by the Contracting Officer or designated Government representative.
Federally Recognized Holidays: The contractor is not anticipated but may be required to provide
service on Federally recognized holidays in accordance with the terms and conditions
established in this PWS to include but not limited to the following:
New Year’s Day Labor Day
Martin Luther King Jr.’s Birthday Columbus Day
President’s Day Veteran’s Day
Memorial Day Thanksgiving Day
Juneteenth Christmas Day
Independence Day
1.4. Place of Performance
Cincinnati VA Medical Center
3200 Vine Street
Cincinnati, Ohio 45220-2637
The work is in building 1 room B013 on the main Cincinnati VA campus.
1.5. Type of Contract
The Government intends to award a firm-fixed-price contract for the services described in this
Performance Work Statement.
Security Requirements and Background Checks: All contractor and subcontractor employees
must comply with Federal, State, Local, and Department of Veterans Affairs security
requirements and background checks to perform services in support of VA medical facilities in
the states of Ohio and Kentucky. Services must be performed in accordance with contract terms
at the contractor’s facility unless otherwise required (e.g., meetings, site visits), which must be
coordinated with the Government Program Manager. Personnel requiring access to any VAMC
property must consent to background checks or will be denied facility access. Required
information for background checks includes: full name, driver’s license number and/or social
security number, date of birth, and a completed background check questionnaire.
AMC/VAACC Identification Badges: The contractor shall ensure that all personnel obtain
VAMC/VAACC identification badges from the VAMC/VAACC security personnel office as
appropriate in compliance with all federal and local VAMC/VAACC facility policies in coordination
with the government program manager if required.
-- 2 of 17 --
Page 3 of 17
Employment Eligibility and Credentialing Requirements: Contractors shall ensure their
employees and those of their Subcontractors possess proper credentials allowing them to work
in the United States. No compensation will be provided for delays or expenses related to
compliance with this requirement. Contractors are not excused from proceeding with the
Contract due to credentialing issues.
POST AWARD CONFERENCE/PERIODIC PROGRESS MEETINGS: The contractor agrees to attend
any post award conference convened by the contracting activity or contract administration
office in accordance with Federal Acquisition Regulation Subpart 42.5. The contracting officer,
government program manager, and other government personnel, as appropriate, may meet
periodically with the contractor to review the contractor's
1.6. Hours and Scheduling
A majority of the generator and emergency power system work shall be performed during
weekends to minimize disruption to medical center operations.
The Contractor shall coordinate all work dates, system outages, switching activities, and testing
with the Government Program Manager, COR, Engineering Service, and other designated VA
personnel before mobilization.
The Contractor shall provide the Government with proposed work dates at least 14 business
days before the planned work, unless otherwise directed by the Contracting Officer.
1.7. Contractor Furnished Items
The Contractor shall furnish all labor, supervision, materials, replacement parts, tools,
equipment, programming devices, test instruments, load banks, transportation, and other items
necessary to complete the work.
The Contractor shall provide a load bank for testing both generators during each scheduled
weekend of work.…
Source: SAM.gov, as posted. Verify the current solicitation before responding.
Pursue this opportunity with Mindy
See who holds it now, who else is bidding, and draft your response — grounded in real government data, not generic AI.
View the original notice on SAM.gov ↗Open opportunities in NAICS 811310
PAINT/SANDING BOOTH, AIR SHOWER, & CABINET BLASTER MAINTENANCE
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due December 15, 2026
J061--Emergency Switchgear Repairs PWS 539
VETERANS AFFAIRS, DEPARTMENT OF · Sources Sought · due December 7, 2026
J061--Eaton Powerware System Replacement
VETERANS AFFAIRS, DEPARTMENT OF · Combined Synopsis/Solicitation · due November 30, 2026
Equipment Operations, Maintenance, and Repair Services at Joint Base Pearl harbor Hickam, Hawaii (JBPHH).
DEPT OF DEFENSE · Solicitation · due December 8, 2026
FIRE EXTINGUISHER INSPECTION, MAINTENANCE, RECHARGE, REPAIR, HYDROSTATIC TESTING
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due December 2, 2026
Crane Hoist and Conductor Bar Upgrade
DEPT OF DEFENSE · Combined Synopsis/Solicitation · due December 9, 2026